SYSTEM.INITIALIZE: BLUEPRINT_UNFOLD
DWG TITLEPORTFOLIO BLUEPRINT
DRAWN BYDINESH KUMAR
SCALE1:1
REVISIONA.02
Back to Simulators
Thermodynamics & HVAC

Psychrometrics Chart Analyzer

Analyze and visualize moist air properties (enthalpy, humidity ratio, specific volume, wet bulb, dew point) dynamically over temperature sweeps and custom climatic presets.

Atm. Pressure
101.325 kPa
Standard Sea Level
Model
ASHRAE / Stull
Moist Air Relations
Output
CSV
Export ready

Parameters

Climatic Presets
Dry-bulb temperature sweep

Psychrometrics Formulations

Saturation Pressure
P_s = 0.61078 * exp(17.27 * T_db / (T_db + 237.3)) kPa
Partial Vapor Pressure
P_v = (RH / 100) * P_s kPa
Humidity Ratio (W)
W = 0.62198 * P_v / (P_atm - P_v) kg/kg
Specific Enthalpy (h)
h = 1.006 * T_db + W * (2501 + 1.84 * T_db) kJ/kg
Specific Volume (v)
v = 0.287042 * (T_db + 273.15) / (P_atm - P_v) m³/kg

At Dry Bulb Temp of 25.0°C and Relative Humidity of 50%, saturation vapor pressure is 3.168 kPa.

Dew Point occurs at 13.9°C (where moisture begins to condense).

Wet Bulb temperature is estimated to be 18.0°C.

Interactive Psychrometric Chart

0°C10°C20°C30°C40°C50°C051015202530Dry Bulb Temperature (°C)Humidity Ratio (g/kg dry air)20% RH40% RH60% RH80% RH25.0°C, 50%
Humidity Ratio (W)
9.88g/kg
Wet Bulb Temperature
18.0°C
Dew Point Temperature
13.9°C
Specific Volume
0.858m³/kg
Mixture Enthalpy (h)
50.3kJ/kg
Vapor Pressure
1.584kPa

Saturation and Relative Humidity Curves

Thermodynamic Curve Data

Dry Bulb Temp (°C)Saturation W (g/kg)50% RH W (g/kg)Current RH W (g/kg)
0.03.771.881.88
2.04.362.172.17
4.05.032.512.51
6.05.792.882.88
8.06.663.313.31
10.07.633.793.79
12.08.734.334.33
14.09.974.954.95
16.011.375.635.63
18.012.936.406.40
20.014.697.267.26
22.016.668.228.22
24.018.879.299.29
26.021.3410.4910.49
28.024.1011.8211.82
30.027.1813.3013.30
32.030.6214.9414.94
34.034.4616.7716.77
36.038.7418.7818.78
38.043.5121.0221.02
40.048.8323.4923.49
42.054.7626.2326.23
44.061.3729.2429.24
46.068.7632.5832.58
48.077.0036.2636.26
50.086.2240.3240.32